关于控制箱的调试,钢制防火卷帘门厂家介绍如下:

来源:http://www.jnyuqilin.com/  发布时间:2019-12-27 11:57:56

 
1、钢制防火卷帘门厂家介绍到进行防火卷帘控制器通电功能测试时,需将防火卷帘控制器分别与消防控制室的火灾报警控制器或消防联动控制设备、相关的火灾探测器、卷门机等连接并通电,这时防火卷帘控制器应处于正常工作状态。
 
 
1. The manufacturer of steel fire shutter introduces that when the fire shutter controller is powered on, it is necessary to connect the fire shutter controller with the fire alarm controller or fire linkage control equipment in the fire control room, relevant fire detector, door rolling machine, etc. and power on. At this time, the fire shutter controller should be in normal working state.
 
2、手动控制防火卷帘门上行、下行、停止及行程开关的调整;在无火警的情况下,按一下“上行”按钮,卷帘门应上行;按一下“下行”按钮,卷帘门应下行;按一下“停止”按钮,卷帘门应停止运行。试运行时,有可能上、下不符,此时只需任意调换两根起闭机的三相接线即可。随后调试相应运行方向的限位是否起作用,不起作用时应调换限位接线;接着调整好行程开关位置,使防火卷帘开闭到位。
 
2. Manually control the adjustment of up, down, stop and travel switch of fire shutter door; in case of no fire, press the "up" button, the shutter door shall go up; press the "down" button, the shutter door shall go down; press the "stop" button, the shutter door shall stop running. During the trial operation, it is possible that the upper and lower parts are inconsistent. At this time, it is only necessary to arbitrarily change the three-phase wiring of the two hoists. Then the position of the corresponding running direction is adjusted, and the limit wiring should be replaced when the effect is not effective. Then the position of the travel switch is adjusted to make the fire shutter open and close.
 
3、接通电源查看“相序/缺相”指示灯是否亮,若灯这应调换电源进线中任意两相,或检醒是否缺相。
 
3. Turn on the power supply to check whether the "phase sequence / missing phase" indicator is on. If the indicator is on, any two phases in the power supply incoming line should be replaced or the phase missing should be detected.
 
4、钢制防火卷帘门厂家告诉大家控制箱基本功能正常后,将门关至下限位观察主板上的绿色指示灯是否亮。若指示灯亮,则可进入电脑记忆调试;若指示灯不亮,则应将上限位和下限位控制线、上行键和下行键控制线以及电机线的任意两条三相线同时对调,直至门归下限位时主板的绿色指示灯亮。
 
4. Steel fire shutter door manufacturers tell you that after the basic function of the control box is normal, close the door to the lower limit and observe whether the green indicator light on the main board is on. If the indicator light is on, you can enter the computer memory debugging; if the indicator light is not on, you should switch the upper limit and lower limit control lines, up key and down key control lines and any two three-phase lines of the motor line at the same time until the green indicator light of the main board is on when the door is at the lower limit.
 
本文来自:济南电动卷帘门安装维修更多的内容请点击:http://www.jnyuqilin.com 我们将会为您提问的问题提供一个满意的服务,欢迎您的来电!
 
This article comes from: installation and maintenance of Jinan electric rolling shutter door. For more information, please click: http://www.jnyuqilin.com  We will provide a satisfactory service for your questions, welcome your call