防火卷帘的联动控制设计符合什么规定?
防火卷帘门具有防火、隔烟、抑制火灾蔓延、保护人员疏散的特殊功能,广泛应用于高层建筑、大型商场等人员密集的场合。那么防火卷帘的联动控制设计符合什么规定?下面
济南防火卷帘门安装维修人员为你解答!
The fireproof rolling shutter door has the special functions of fire prevention, smoke separation, fire prevention and evacuation protection, and is widely used in high-rise buildings, shopping malls and other crowded places. What regulations does the linkage control design of the fire shutter meet? The following Jinan fire shutter door installation and maintenance personnel to answer for you!
用于疏散通道的防火卷帘控制器应具有两步关闭的功能,并应向消防联动控制器发出反馈信号。防火卷帘控制器接收到首次火灾报警信号后,应能控制防火卷帘自动关闭到中位处停止;接收到二次报警信号后,应能控制防火卷帘继续关闭至全闭状态。
The fire shutter controller used for evacuation passage shall have the function of two-step closing, and shall send feedback signals to the fire linkage controller. After receiving the first fire alarm signal, the fire shutter controller shall be able to control the fire shutter to automatically close to the middle position and stop; After receiving the secondary alarm signal, it shall be able to control the fire shutter to continue to close to the fully closed state.
用于分隔防火分区的防火卷帘控制器在接收到防火分区内任一火灾报警信号后,应能控制防火卷帘到全关闭状态,并应向消防联动控制器发出反馈信号。
After receiving any fire alarm signal in the fire compartment, the fire shutter controller used to separate the fire compartment shall be able to control the fire shutter to the fully closed state, and shall send a feedback signal to the fire linkage controller.
1.防火卷帘的升降应由防火卷帘控制器控制。
1. The lifting of fire shutter shall be controlled by fire shutter controller.
2.疏散通道上设置的防火卷帘的联动控制设计,应符合下列规定:
2. The linkage control design of the fire shutter set on the evacuation exit shall meet the following requirements:
(1)、联动控制方式,防火分区内任两只独立的感烟火灾探测器或任一只专门用于联动防火卷帘的感烟火灾探测器的报警信号应联动控制防火卷帘下降至距楼板面1.8m处;任一只专门用于联动防火卷帘的感温火灾探测器的报警信号应联动控制防火卷帘下降到楼板面;在卷帘的任一侧距卷帘纵深0.5m~5m内应设置不少于2只专门用于联动防火卷帘的感温火灾探测器。
(1) Linkage control mode: the alarm signal of any two independent smoke fire detectors or any smoke fire detector specially used for linkage fire shutter in the fire compartment shall be linked to control the fire shutter to descend to 1.8m from the floor; The alarm signal of any temperature fire detector specially used for linkage fire shutter shall be linked to control the fire shutter to descend to the floor; At least 2 heat fire detectors specially used for linkage fire shutter shall be set within 0.5m~5m from either side of the shutter to the depth of the shutter.
(2)、手动控制方式,应由防火卷帘两侧设置的手动控制按钮控制防火卷帘的升降。
(2) In manual control mode, the lifting and lowering of the fire shutter shall be controlled by the manual control buttons set on both sides of the fire shutter.
3.非疏散通道上设置的防火卷帘的联动控制设计,应符合下列规定:
3. The linkage control design of the fire shutter set on the non evacuation exit shall meet the following requirements:
(1)联动控制方式,应由防火卷帘所在防火分区内任两只独立的火灾探测器的报警信号,作为防火卷帘下降的联动触发信号,并应联动控制防火卷帘直接下降到楼板面。
(1) In linkage control mode, the alarm signal of any two independent fire detectors in the fire compartment where the fire shutter is located shall be used as the linkage trigger signal for the fire shutter to descend, and the fire shutter shall be controlled to descend directly to the floor.
(2)手动控制方式,应由防火卷帘两侧设置的手动控制按钮控制防火卷帘的升降,并应能在消防控制室内的消防联动控制器上手动控制防火卷帘的降落。
(2) For manual control mode, the manual control buttons set at both sides of the fire shutter shall control the lifting and lowering of the fire shutter, and the fire linkage controller in the fire control room shall be able to manually control the lowering of the fire shutter.
4.防火卷帘下降至距楼板面1.8m处、下降到楼板面的动作信号和防火卷帘控制器直接连接的感烟、感温火灾探测器的报警信号,应反馈至消防联动控制器。
4. The action signal of the fire shutter descending to 1.8m from the floor and the alarm signal of the smoke and temperature detectors directly connected to the fire shutter controller shall be fed back to the fire linkage controller.
What regulations does the linkage control design of fire shutter meet? The above is the answer to the question. If you have any questions, please contact us at any time http://www.jnyuqilin.com Understand!